HDW-750 T5
747 kVA Generator set Open Skid
Powered by: HYUNDAI
Alternator: STAMFORD
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 633kW prp ; 699kW standby
- Manufacturer: HYUNDAI
- Model: DP222LCF
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 12-V
- Bore and Stroke: 128 x 142 mm
- Displacement: 21,927 L
- Cooling System: Coolant
- Lube Oil Specifications: API CH4 SAE 15W40 or 10W40
- Compression Ratio: 15:1
- Fuel Consumption ESP: 172,8 l/h
- Fuel Consumption 100% PRP: 161 l/h
- Fuel Consumption 75 % PRP: 119,1 l/h
- Fuel Consumption 50 % PRP: 79,3 l/h
- Fuel Consumption 25 % PRP: 42,1 l/h
- Lube oil consumption with full load: 0,5 % of fuel consumption
- Total oil capacity: 40 L
- Total coolant capacity: 114 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Radiator water level sensor (Optional)
- Generator: STAMFORD
- Model: S6L1D.C4
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Elastic Coupling
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 502 ºC
- Exhaust Gas Flow: 108 m3/min
- Maximum allowed back pressure: 5,9 kPa
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 2700 m3/h
- Cooling Air Flow: 14,33 m3/s
- Alternator fan air flow: 1,46 m3/s
- - STARTING SYSTEM.
- Starting power: 7 kW
- Starting power: 9,52 CV
- Recommended battery: 200 x 2 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 225 mm Hg
- Maximum return feed pump: 450 mm Hg
- Fuel Tank: 875 L
- - DIMENSIONS.
- Length: 4.200 mm
- Height: 2.310 mm
- Width: 1.600 mm
- Maximum shipping volume: 15,52 m3
- Weight with liquids in radiator and sump: 4.774 kg
- Fuel tank capacity: 875 L
- Autonomy: 7 Hours
Power
kVA
747
823
Prime power (199 - 1034)
Stand by (220 - 1145)
Stand by (220 - 1145)
kW
598
659
Prime power (159 - 827)
Stand by (176 - 916)
Stand by (176 - 916)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
420
Width (B)
160
High (C)
231
Long (A)
165,35
Width (B)
62,99
High (C)
90,94
Weight
Weight with liquid in radiator and carter
4.774 10.526,67
4.774 10.526,67
Fuel capacity
875
231