HGS-405 T5 BIO

 

HGS-405 T5 BIO

404 kVA COP Generator set Soundproof

Powered by: SIEMENS
Alternator: STAMFORD

 

Three phase | 50 Hz | Biogas |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Engine Output: 419kW cop
  • Manufacturer: SIEMENS
  • Model: SGE24SL
  • Engine Type: 4-stroke Otto Cycle
  • Injection Type: Carburization
  • Aspiration Type: Turbocharged
  • Number of cylinders and arrangement: 8-L
  • Bore and Stroke: 152 x 165 mm
  • Displacement: 24 L
  • Cooling System: Water + Antifreeze
  • Lube Oil Specifications: SAE 40
  • Compression Ratio: 11,6
  • Fuel Consumption 100% PRP: 1061 kW
  • Fuel Consumption 80 % PRP: 871 kW
  • Fuel Consumption 75 % PRP: 841,26 kW
  • Fuel Consumption 50 % PRP: 595,87 kW
  • Fuel Consumption 25 % PRP: 353,92 kW
  • Lube oil consumption with full load: 0,35
  • Total oil capacity: 116 L
  • Governor Type Electrical
  • Air Filter Type Semi-humid
  • Biogas Engine
  • 4-stroke cycle
  • Water-cooled
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Hot parts protection
  • Moving parts protection
  • Generator: STAMFORD
  • Model: HCI544E
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-0 18''
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Double drive-shaft
  • Coupling system: Elastic Coupling
  • Coating type: Standard (Vacuum impregnation)
  • - CONTAINER VERSION.
  • Soundproofing provided by high-density volcanic rock wool
  • High mechanical resistance
  • Low level of noise emissions
  • Door with window to visualize control panel, alarms and measurements
  • Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
  • Residential steel silencer with -35dB attenuation and tilting cap in the exhaust
  • Anti-vibration shock absorbers
  • Steel chassis
  • Manual oil extraction pump
  • Robust construction designed for continuous or emergency applications
  • Emergency stops
  • Easy access to the power connection
  • Reinforced chassis for heavy range
  • Easy access for chassis cleaning
  • - GAS RAMP.
  • Manual shut-off valve
  • Double solenoid valve
  • High pressure regulator
  • Primary pressure regulator
  • Secondary pressure regulator (Zero pressure regulator)
  • Low pressure switch
  • High pressure switch
  • Valve (tightness) testing system
  • Inlet pressure manometer
  • Outlet pressure manometer
  • Special Start/Stop sequence
  • - ELECTRICAL SYSTEM CONTAINER.
  • Control panel and emergency stop button
  • Power panel
  • Battery charger (standard on automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charge alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Battery isolator
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 378 ºC
  • Exhaust Gas Flow: 0,6 kg/s
  • Maximum allowed back pressure: 450 mm H2o
  • - NECESSARY AMOUNT OF AIR.
  • Cooling Air Flow: 8,147 m3/s
  • Alternator fan air flow: 1,035 m3/s
  • - STARTING SYSTEM.
  • Auxiliary Voltage: 12 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Biogas
  • - DIMENSIONS.
  • Length: 6.058 mm
  • Height: 2.896 mm
  • Width: 2.438 mm
  • Maximum shipping volume: 42,77 m3

Power


 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
605,80
Width (B)
243,80
High (C)
289,60
 

Weight


 
Weight
Weight with liquid in radiator and carter

0
 

Fuel capacity