HSY-50 T5
41 kVA Generator set Open Skid
Powered by: YANMAR
Alternator: MECC ALTE
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 37,7kW prp ; 45,5kW standby
- Manufacturer: YANMAR
- Model: 4TNV98THSPU
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged
- Number of cylinders and arrangement: 4-L
- Bore and Stroke: 98 x 110 mm
- Displacement: 3,319 L
- Cooling System: Coolant
- Lube Oil Specifications: SAE 3 class 10W30 / API grade CD,CF
- Compression Ratio: 18,1
- Fuel Consumption ESP: 10,74 l/h
- Fuel Consumption 100% PRP: 9,16 l/h
- Fuel Consumption 75 % PRP: 6,94 l/h
- Fuel Consumption 50 % PRP: 4,89 l/h
- Lube oil consumption with full load: 0,27
- Total oil capacity: 10,5 L
- Total coolant capacity: 9 L
- Governor Type Mechanical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 45 mm
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Dry air filter
- Radiator with pusher fan
- Mechanical governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECP32.2S4C
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Steel industrial silencer -15db(A) attenuation
- Manual oil drain pump (Optional)
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- Optional Battery (Optima) (Optional)
- Leakage detector (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 480 ºC
- Exhaust Gas Flow: 11,36 m3/min
- Maximum allowed back pressure: 1000 mm H2o
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 194,16 m3/h
- Cooling Air Flow: 0,979 m3/s
- Alternator fan air flow: 0,261 m3/s
- - STARTING SYSTEM.
- Starting power: 2,3 kW
- Starting power: 3,13 CV
- Recommended battery: 92 Ah
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 120 L
- - DIMENSIONS.
- Length: 1.850 mm
- Height: 1.500 mm
- Width: 780 mm
- Maximum shipping volume: 2,16 m3
- Weight with liquids in radiator and sump: 665 kg
- Fuel tank capacity: 120 L
- Autonomy: 17 Hours
Power
kVA
41
50
Prime power (7.2 - 51)
Stand by (7.3 - 59)
Stand by (7.3 - 59)
kW
33
40
Prime power (5.8 - 41)
Stand by (6.2 - 48)
Stand by (6.2 - 48)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
185
Width (B)
78
High (C)
150
Long (A)
72,83
Width (B)
30,71
High (C)
59,06
Weight
Weight with liquid in radiator and carter
665 1.466,33
665 1.466,33
Fuel capacity
120
31,68