HFW-125 T5
120 kVA Generator set Open Skid
Powered by: FPT_IVECO
Alternator: STAMFORD
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 107,2kW prp ; 118,2kW standby
- Manufacturer: FPT_IVECO
- Model: NEF45TM3
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 4-L
- Bore and Stroke: 104 x 132 mm
- Displacement: 4,5 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: ACEA E3 - E5
- Compression Ratio: 17,5:1
- Fuel Consumption ESP: 30,4 l/h
- Fuel Consumption 100% PRP: 27,6 l/h
- Fuel Consumption 80 % PRP: 21,6 l/h
- Fuel Consumption 50 % PRP: 14,4 l/h
- Lube oil consumption with full load: 0,5 % of fuel consumption
- Total oil capacity including tubes, filters 12,8 L
- Total coolant capacity: 18,5 L
- Governor Type Mechanical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 70,3 mm
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- Mechanical governor
- Hot parts protection
- Moving parts protection
- Radiator water level sensor (Optional)
- HTW sender (Optional)
- LOP sender (Optional)
- Generator: STAMFORD
- Model: UCI274D
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- High mechanical strength
- Epoxy polyester powder coating
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 540 ºC
- Maximum allowed back pressure: 5 kPa
- Heat dissipated by exhaust pipe: 590 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 427 m3/h
- Cooling Air Flow: 2,2 m3/s
- Alternator fan air flow: 0,514 m3/s
- - STARTING SYSTEM.
- Starting power: 3 kW
- Starting power: 4,08 CV
- Recommended battery: 100 Ah
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 170 L
- - DIMENSIONS.
- Length: 2.450 mm
- Height: 1.512 mm
- Width: 780 mm
- Maximum shipping volume: 2,89 m3
- Weight with liquids in radiator and sump: 1.162 kg
- Fuel tank capacity: 170 L
- Autonomy: 8 Hours
Power
kVA
120
130
Prime power (60 - 598)
Stand by (63 - 657)
Stand by (63 - 657)
kW
96
104
Prime power (48 - 478)
Stand by (50 - 525)
Stand by (50 - 525)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
245
Width (B)
78
High (C)
151,20
Long (A)
96,46
Width (B)
30,71
High (C)
59,53
Weight
Weight with liquid in radiator and carter
1.162 2.562,21
1.162 2.562,21
Fuel capacity
170
44,88