HTW-765 T5
761 kVA Generator set Open Skid
Powered by: MITSUBISHI
Alternator: STAMFORD
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 645kW prp ; 710kW standby
- Manufacturer: MITSUBISHI
- Model: S6R2 PTAA
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 170 x 220 mm
- Displacement: 29,96 L
- Cooling System: Water
- Lube Oil Specifications: API CD or CF SAE 30 or SAE 40
- Compression Ratio: 14:01
- Fuel Consumption ESP: 175,16 l/h
- Fuel Consumption 100% PRP: 157,08 l/h
- Fuel Consumption 75 % PRP: 118,58 l/h
- Fuel Consumption 50 % PRP: 82,11 l/h
- Fuel Consumption 25 % PRP: 47,94 l/h
- Lube oil consumption with full load: 0,8
- Total oil capacity including tubes, filters 94 L
- Total coolant capacity: 132 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 205 mm
- Oil temperature sensor
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: S6L1D.C4
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-0 18''
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Water Jacket Heater with single phase pump
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 520 ºC
- Exhaust Gas Flow: 171 m3/min
- Maximum allowed back pressure: 600 mm H2o
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 3900 m3/h
- Cooling Air Flow: 12 m3/s
- - STARTING SYSTEM.
- Starting power: 7,5 kW
- Starting power: 10,2 CV
- Recommended battery: 250 Ah
- Auxiliary Voltage: 24 Vdc
- Starter current peak: 700 A
- Nominal starter current: 370 A
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 75 mm Hg
- Maximum return feed pump: 150 mm Hg
- - DIMENSIONS.
- Length: 4.098 mm
- Height: 1.940 mm
- Width: 1.750 mm
- Maximum shipping volume: 13,91 m3
- Weight with liquids in radiator and sump: 6.070 kg
Power
kVA
761
836
Prime power (670 - 2555)
Stand by (738 - 2816)
Stand by (738 - 2816)
kW
609
669
Prime power (536 - 2044)
Stand by (590 - 2253)
Stand by (590 - 2253)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
409,80
Width (B)
175
High (C)
194
Long (A)
161,34
Width (B)
68,90
High (C)
76,38
Weight
Weight with liquid in radiator and carter
6.070 13.384,35
6.070 13.384,35
Fuel capacity
0