HGP-170 T5 LPG
167 kVA Generator set Open Skid
Powered by: PSI
Alternator: STAMFORD
Three phase | 50 Hz | LPG |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 144,3kW prp ; 161,3kW standby
- Manufacturer: PSI
- Model: 14.6L
- Engine Type: 4-stroke Otto Cycle
- Injection Type: Carburization
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 8-V
- Bore and Stroke: 128 x 142 mm
- Displacement: 14,6 L
- Cooling System: Coolant
- Lube Oil Specifications: API CD/≥CF, SAE 15W40
- Compression Ratio: 10,5:1
- Total oil capacity including tubes, filters 38,1 L
- Total coolant capacity: 127 L
- Governor Type Electrical
- Air Filter Type Dry
- LPG-liquefied petrol gas engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: UCI274G
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Steel industrial silencer -15db(A) attenuation
- Steel residential silencer -35db(A) attenuation. (Optional)
- - GAS RAMP.
- Manual shut-off valve
- Gas filter
- Double solenoid valve
- Primary pressure regulator
- Secondary pressure regulator (Zero pressure regulator)
- Low pressure switch
- Valve (tightness) testing system
- Inlet pressure manometer
- Outlet pressure manometer
- Special Start/Stop sequence
- High pressure regulator (Optional)
- High pressure switch (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 750 ºC
- Exhaust Gas Flow: 45,2 m3/min
- Maximum allowed back pressure: 10,2 kPa
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 840 m3/h
- Alternator fan air flow: 0,514 m3/s
- - STARTING SYSTEM.
- Starting power: 7 kW
- Starting power: 9,52 CV
- Recommended battery: 200 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: LPG
- - DIMENSIONS.
- Length: 3.610 mm
- Height: 1.929 mm
- Width: 1.651 mm
- Maximum shipping volume: 11,5 m3
- Weight with liquids in radiator and sump: 3.276 kg
Power
kVA
167
186
Prime power (95 - 1183)
Stand by (105 - 1322)
Stand by (105 - 1322)
kW
133
149
Prime power (76 - 947)
Stand by (84 - 1058)
Stand by (84 - 1058)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
361
Width (B)
165,10
High (C)
192,90
Long (A)
142,13
Width (B)
65
High (C)
75,94
Weight
Weight with liquid in radiator and carter
3.276 7.223,58
3.276 7.223,58
Fuel capacity
0