HMW-605 T5

 

HMW-605 T5

601 kVA Generator set Open Skid

Powered by: MTU
Alternator: STAMFORD

 

Three phase | 50 Hz | Diesel |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Engine Output: 506kW prp ; 558kW standby
  • Manufacturer: MTU
  • Model: 12V1600G10F
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 12-V
  • Bore and Stroke: 122 x 150 mm
  • Displacement: 21 L
  • Cooling System: Coolant
  • Lube Oil Specifications: S10 W40
  • Compression Ratio: 17,5
  • Fuel Consumption ESP: 128,6 l/h
  • Fuel Consumption 100% PRP: 116,99 l/h
  • Fuel Consumption 75 % PRP: 90,94 l/h
  • Fuel Consumption 50 % PRP: 63,06 l/h
  • Fuel Consumption 25 % PRP: 34,58 l/h
  • Lube oil consumption with full load: 0,5 % of fuel consumption
  • Total oil capacity including tubes, filters 72,5 L
  • Total coolant capacity: 99 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Inner diameter exhaust pipe: 106 mm
  • Diesel engine
  • 4-stroke cycle
  • 24V electrical system
  • Water separator filter (visible level)
  • Dry air filter
  • Radiator with pusher fan
  • Radiator water level sensor
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Generator: STAMFORD
  • Model: HCI544E
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-1 14"
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Battery Switch
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 482 ºC
  • Exhaust Gas Flow: 102 m3/min
  • Maximum allowed back pressure: 150 mbar
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 2880 m3/h
  • Cooling Air Flow: 11,2 m3/s
  • Alternator fan air flow: 1,035 m3/s
  • - STARTING SYSTEM.
  • Starting power: 8 kW
  • Starting power: 10,88 CV
  • Recommended battery: 75 x 2 Ah
  • Auxiliary Voltage: 24 Vdc
  • Starter current peak: 800 A
  • Nominal starter current: 250 A
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Fuel Tank: 740 L
  • - DIMENSIONS.
  • Length: 3.600 mm
  • Height: 2.121 mm
  • Width: 1.604 mm
  • Maximum shipping volume: 12,25 m3
  • Weight with liquids in radiator and sump: 4.529 kg
  • Fuel tank capacity: 740 L
  • Autonomy: 8 Hours

Power


kVA

601
 
660
Prime power  (457 - 2572)
Stand by  (504 - 2809)

kW

481
 
528
Prime power  (365 - 2058)
Stand by  (403 - 2247)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
360
Width (B)
160,40
High (C)
212,10
 

Weight


 
Weight
Weight with liquid in radiator and carter

4.529
 

Fuel capacity


 
 
740