HFW-200 T5

 

HFW-200 T5

200 kVA Generator set Open Skid

Powered by: FPT_IVECO
Alternator: STAMFORD

 

Three phase | 50 Hz | Diesel | Stage 3A

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Engine Output: 138,5kW cop ; 174,9kW prp ; 193,1kW standby
  • Manufacturer: FPT_IVECO
  • Model: N67.TE3PV
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct, common rail
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 6-L
  • Bore and Stroke: 104 x 132 mm
  • Displacement: 6,7 L
  • Cooling System: Coolant
  • Lube Oil Specifications: 10W40 CJ4 / CK4 ACEA E9
  • Compression Ratio: 16,5:1
  • Fuel Consumption ESP: 47,6 l/h
  • Fuel Consumption 100% PRP: 43,9 l/h
  • Fuel Consumption 80 % PRP: 41,2 l/h
  • Fuel Consumption 50 % PRP: 29,4 l/h
  • Fuel Consumption 25 % PRP: 14,1 l/h
  • Lube oil consumption with full load: 0,3 % of fuel consumption
  • Total oil capacity including tubes, filters 17 L
  • Total coolant capacity: 36,2 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 12V electrical system
  • Water separator filter (no visible level)
  • Dry air filter
  • Radiator with pusher fan
  • Radiator water level sensor
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Generator: STAMFORD
  • Model: UCI274H
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-3 11"1/2
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Oil sump extraction kit
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • High mechanical strength
  • Epoxy polyester powder coating
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Battery Switch
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 600 ºC
  • Maximum allowed back pressure: 20 kPa
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 682,35 m3/h
  • Cooling Air Flow: 3,8 m3/s
  • Alternator fan air flow: 0,514 m3/s
  • - STARTING SYSTEM.
  • Auxiliary Voltage: 12 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Fuel Tank: 250 L
  • - DIMENSIONS.
  • Length: 2.900 mm
  • Height: 1.634 mm
  • Width: 900 mm
  • Maximum shipping volume: 4,26 m3
  • Weight with liquids in radiator and sump: 1.570 kg
  • Fuel tank capacity: 250 L
  • Autonomy: 6 Hours

Power


kVA

200
 
220
Prime power  (60 - 598)
Stand by  (63 - 657)

kW

160
 
176
Prime power  (48 - 478)
Stand by  (50 - 525)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
290
Width (B)
90
High (C)
163,40
 

Weight


 
Weight
Weight with liquid in radiator and carter

1.570
 

Fuel capacity


 
 
250