HBW-455 T5

 

HBW-455 T5

458 kVA Generator set Open Skid

Powered by: BAUDOUIN
Alternator: STAMFORD

 

Three phase | 50 Hz | Diesel |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Engine Output: 391kW prp ; 432kW standby
  • Manufacturer: BAUDOUIN
  • Model: 6M21G500.5
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 6-L
  • Bore and Stroke: 127 x 165 mm
  • Displacement: 12,54 L
  • Cooling System: Liquid (water + 50% glycol)
  • Lube Oil Specifications: API CF or CH4, SAE 15W-40
  • Compression Ratio: 16:1
  • Fuel Consumption ESP: 110,2 l/h
  • Lube oil consumption with full load: 0,2 % of fuel consumption
  • Total oil capacity including tubes, filters 32 L
  • Total coolant capacity: 55 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Inner diameter exhaust pipe: 160 mm
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 24V electrical system
  • Water separator filter (no visible level)
  • Dry air filter
  • Radiator with pusher fan
  • Radiator water level sensor
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Generator: STAMFORD
  • Model: HCI544C
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-1 14"
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Battery Switch
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 580 ºC
  • Exhaust Gas Flow: 99 m3/min
  • Maximum allowed back pressure: 120 mbar
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 1722 m3/h
  • Cooling Air Flow: 9,17 m3/s
  • Alternator fan air flow: 1,035 m3/s
  • - STARTING SYSTEM.
  • Starting power: 8,5 kW
  • Starting power: 11,56 CV
  • Recommended battery: 50 x 2 Ah
  • Auxiliary Voltage: 24 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Maximum power suction pump: 375 mm Hg
  • Maximum return feed pump: 375 mm Hg
  • Fuel Tank: 740 L
  • - DIMENSIONS.
  • Length: 3.600 mm
  • Height: 1.890 mm
  • Width: 1.460 mm
  • Maximum shipping volume: 9,93 m3
  • Weight with liquids in radiator and sump: 3.108 kg
  • Fuel tank capacity: 740 L

Power


kVA

458
 
505
Prime power  (155 - 1385)
Stand by  (170 - 1523)

kW

367
 
404
Prime power  (124 - 1108)
Stand by  (136 - 1218)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
360
Width (B)
146
High (C)
189
 

Weight


 
Weight
Weight with liquid in radiator and carter

3.108
 

Fuel capacity


 
 
740