HFW-100 T5

 

HFW-100 T5

100 kVA Generator set Open Skid

Powered by: FPT_IVECO
Alternator: STAMFORD

 

Three phase | 50 Hz | Diesel | Stage 2

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Engine Output: 88,6kW prp ; 95,9kW standby
  • Manufacturer: FPT_IVECO
  • Model: NEF45TM2A
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 4-L
  • Bore and Stroke: 104 x 132 mm
  • Displacement: 4,5 L
  • Cooling System: Liquid (water + 50% glycol)
  • Lube Oil Specifications: ACEA E3 - E5
  • Compression Ratio: 17,5 : 1
  • Fuel Consumption ESP: 24,4 l/h
  • Fuel Consumption 100% PRP: 22 l/h
  • Fuel Consumption 80 % PRP: 16,2 l/h
  • Fuel Consumption 50 % PRP: 11 l/h
  • Lube oil consumption with full load: 0,5 % of fuel consumption
  • Total oil capacity including tubes, filters 12,8 L
  • Total coolant capacity: 18,5 L
  • Governor Type Mechanical
  • Air Filter Type Dry
  • Inner diameter exhaust pipe: 70,3 mm
  • Diesel engine
  • 4-stroke cycle
  • 12V electrical system
  • Water separator filter (no visible level)
  • Dry air filter
  • Radiator with pusher fan
  • Mechanical governor
  • Hot parts protection
  • Moving parts protection
  • Radiator water level sensor (Optional)
  • HTW sender (Optional)
  • LOP sender (Optional)
  • Generator: STAMFORD
  • Model: UCI274C
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-3 11"1/2
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Oil sump extraction kit
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • High mechanical strength
  • Epoxy polyester powder coating
  • Fuel tank drain plug
  • Steel industrial silencer -15db(A) attenuation
  • Fuel transfer pump (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Battery Switch (Optional)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 535 ºC
  • Exhaust Gas Flow: 0,148 kg/s
  • Maximum allowed back pressure: 5 kPa
  • Heat dissipated by exhaust pipe: 731,6 KCal/Kwh
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 427 m3/h
  • Cooling Air Flow: 2,2 m3/s
  • Alternator fan air flow: 0,514 m3/s
  • - STARTING SYSTEM.
  • Starting power: 3 kW
  • Starting power: 4,08 CV
  • Recommended battery: 100 Ah
  • Auxiliary Voltage: 12 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Fuel Tank: 145 L
  • - DIMENSIONS.
  • Length: 2.150 mm
  • Height: 1.500 mm
  • Width: 780 mm
  • Maximum shipping volume: 2,52 m3
  • Weight with liquids in radiator and sump: 1.109 kg
  • Fuel tank capacity: 145 L
  • Autonomy: 9 Hours

Power


kVA

100
 
107
Prime power  (60 - 598)
Stand by  (63 - 657)

kW

80
 
86
Prime power  (48 - 478)
Stand by  (50 - 525)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
215
Width (B)
78
High (C)
150
 

Weight


 
Weight
Weight with liquid in radiator and carter

1.109
 

Fuel capacity


 
 
145