HTW-1900 T5

 

HTW-1900 T5

1892 kVA Generator set Open Skid

Powered by: MITSUBISHI
Alternator: STAMFORD

 

Three phase | 50 Hz | Diesel |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Engine Output: 1580kW prp ; 1740kW standby
  • Manufacturer: MITSUBISHI
  • Model: S16R PTA2
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 16-V
  • Bore and Stroke: 170 x 180 mm
  • Displacement: 65,37 L
  • Cooling System: Water
  • Lube Oil Specifications: API CD or CF SAE 30 or SAE 40
  • Compression Ratio: 13,5:1
  • Fuel Consumption ESP: 423,75 l/h
  • Fuel Consumption 100% PRP: 387,28 l/h
  • Fuel Consumption 75 % PRP: 297,96 l/h
  • Fuel Consumption 50 % PRP: 209,88 l/h
  • Fuel Consumption 25 % PRP: 121,18 l/h
  • Lube oil consumption with full load: 0,8
  • Total oil capacity including tubes, filters 230 L
  • Total coolant capacity: 445 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Inner diameter exhaust pipe: 340 mm
  • Oil temperature sensor
  • Low coolant level sensor
  • Exhaust gas compensator
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 24V electrical system
  • Standard air filter
  • Standard fuel filter
  • Standard oil filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Generator: STAMFORD
  • Model: PI734E
  • Poles: 4
  • Connection type (standard): Star
  • Mounting type: S-00 21"
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Oil sump extraction kit
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
  • Maintenance-free and anti-explosion battery
  • Battery Switch
  • Battery charger (standard on gensets with automatic control panels)
  • Water Jacket Heater with single phase pump
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 560 ºC
  • Exhaust Gas Flow: 379 m3/min
  • Maximum allowed back pressure: 600 mm H2o
  • Heat dissipated by exhaust pipe: 587,2 KCal/Kwh
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 8580 m3/h
  • Cooling Air Flow: 34 m3/s
  • Alternator fan air flow: 2,69 m3/s
  • - STARTING SYSTEM.
  • Starting power: 7,5 x 2 kW
  • Starting power: 10,2 x 2 CV
  • Recommended battery: 400 Ah
  • Auxiliary Voltage: 24 Vdc
  • Starter current peak: 1250 A
  • Nominal starter current: 400 A
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • Maximum power suction pump: 75 mm Hg
  • Maximum return feed pump: 150 mm Hg
  • - DIMENSIONS.
  • Length: 5.566 mm
  • Height: 2.520 mm
  • Width: 2.290 mm
  • Maximum shipping volume: 32,12 m3
  • Weight with liquids in radiator and sump: 12.150 kg

Power


kVA

1892
 
2035
Prime power  (670 - 2555)
Stand by  (738 - 2816)

kW

1514
 
1628
Prime power  (536 - 2044)
Stand by  (590 - 2253)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
556,60
Width (B)
229
High (C)
252
 

Weight


 
Weight
Weight with liquid in radiator and carter

12.150
 