HMW-1135 T5
1135 kVA Generator set Open Skid
Powered by: MTU
Alternator: STAMFORD
Three phase | 50 Hz | Diesel |
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 952kW prp ; 1052kW standby
- Manufacturer: MTU
- Model: 18V2000G65
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 18-V
- Bore and Stroke: 130 x 150 mm
- Displacement: 35,82 L
- Cooling System: Coolant
- Lube Oil Specifications: S10 W40
- Compression Ratio: 16
- Fuel Consumption ESP: 260,93 l/h
- Fuel Consumption 100% PRP: 234,88 l/h
- Fuel Consumption 75 % PRP: 174,42 l/h
- Fuel Consumption 50 % PRP: 118,6 l/h
- Fuel Consumption 25 % PRP: 64,53 l/h
- Lube oil consumption with full load: 1 % of fuel consumption
- Total oil capacity including tubes, filters 130 L
- Total coolant capacity: 216 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 140,5 mm
- Electronic management (ADEC)
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: HCI634K
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-0 18''
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Fuel transfer pump (Optional)
- Steel industrial silencer -15db(A) attenuation (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 575 ºC
- Exhaust Gas Flow: 216 m3/min
- Maximum allowed back pressure: 85 mbar
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 4500 m3/h
- Cooling Air Flow: 25,2 m3/s
- Alternator fan air flow: 1,614 m3/s
- - STARTING SYSTEM.
- Starting power: 9,5 kW
- Starting power: 12,92 CV
- Recommended battery: 260 Ah
- Auxiliary Voltage: 24 Vdc
- Starter current peak: 1600 A
- Nominal starter current: 800 A
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- - DIMENSIONS.
- Length: 5.050 mm
- Width: 1.910 mm
Power
kVA
1135
1262
Prime power (601 - 2572)
Stand by (660 - 2809)
Stand by (660 - 2809)
kW
908
984
Prime power (481 - 2058)
Stand by (528 - 2247)
Stand by (528 - 2247)
Sound level
dB
Distance (m)
Distance (m)
dimensions
Long (A)
505
Width (B)
191
High (C)
0
Long (A)
198,82
Width (B)
75,20
High (C)
0
Weight
Weight with liquid in radiator and carter
0 0
0 0
Fuel capacity
0
0