HMW-1135 T5

 

HMW-1135 T5

1135 kVA Generator set Open Skid

Powered by: MTU
Alternator: STAMFORD

 

Three phase | 50 Hz | Diesel |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Engine Output: 952kW prp ; 1052kW standby
  • Manufacturer: MTU
  • Model: 18V2000G65
  • Engine Type: 4-stroke diesel
  • Injection Type: Direct
  • Aspiration Type: Turbocharged and after-cooled
  • Number of cylinders and arrangement: 18-V
  • Bore and Stroke: 130 x 150 mm
  • Displacement: 35,82 L
  • Cooling System: Coolant
  • Lube Oil Specifications: S10 W40
  • Compression Ratio: 16
  • Fuel Consumption ESP: 260,93 l/h
  • Fuel Consumption 100% PRP: 234,88 l/h
  • Fuel Consumption 75 % PRP: 174,42 l/h
  • Fuel Consumption 50 % PRP: 118,6 l/h
  • Fuel Consumption 25 % PRP: 64,53 l/h
  • Lube oil consumption with full load: 1 % of fuel consumption
  • Total oil capacity including tubes, filters 130 L
  • Total coolant capacity: 216 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Inner diameter exhaust pipe: 140,5 mm
  • Electronic management (ADEC)
  • Low coolant level sensor
  • Exhaust gas compensator
  • Diesel engine
  • 4-stroke cycle
  • Water-cooled
  • 24V electrical system
  • Standard air filter
  • Standard fuel filter
  • Standard oil filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Hot parts protection
  • Moving parts protection
  • Generator: STAMFORD
  • Model: HCI634K
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-0 18''
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - OPEN SET VERSION.
  • Steel chassis
  • Emergency stop button
  • Oil sump extraction kit
  • Anti-vibration shock absorbers
  • Chassis with integrated fuel tank
  • Fuel level gauge
  • Fuel tank drain plug
  • Fuel transfer pump (Optional)
  • Steel industrial silencer -15db(A) attenuation (Optional)
  • Steel residential silencer -35db(A) attenuation. (Optional)
  • - ELECTRICAL SYSTEM.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
  • Maintenance-free and anti-explosion battery
  • Battery Switch
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 575 ºC
  • Exhaust Gas Flow: 216 m3/min
  • Maximum allowed back pressure: 85 mbar
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 4500 m3/h
  • Cooling Air Flow: 25,2 m3/s
  • Alternator fan air flow: 1,614 m3/s
  • - STARTING SYSTEM.
  • Starting power: 9,5 kW
  • Starting power: 12,92 CV
  • Recommended battery: 260 Ah
  • Auxiliary Voltage: 24 Vdc
  • Starter current peak: 1600 A
  • Nominal starter current: 800 A
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Diesel
  • - DIMENSIONS.
  • Length: 5.050 mm
  • Width: 1.910 mm

Power


kVA

1135
 
1262
Prime power  (601 - 2572)
Stand by  (660 - 2809)

kW

908
 
984
Prime power  (481 - 2058)
Stand by  (528 - 2247)
 

Sound level

 dB
 Distance (m)

 
 

dimensions


 
dimensions
Long (A)
505
Width (B)
191
High (C)
0
 

Weight


 
Weight
Weight with liquid in radiator and carter

0
 

Fuel capacity


 
 