HGP-100 T5 NG

 

HGP-100 T5 NG

95 kVA Generator set Open Skid

Powered by: PSI
Alternator: STAMFORD

 

Three phase | 50 Hz | Natural Gas |

 

 

  • Engine Specifications 1.500 r.p.m.
  • Rated Output: 0kW cop ; 83,7kW prp ; 93,8kW standby
  • Manufacturer: PSI
  • Model: 8.8L NA
  • Engine Type: 4-stroke Otto Cycle
  • Injection Type: Carburization
  • Aspiration Type: Natural
  • Number of cylinders and arrangement: 8 - V
  • Bore and Stroke: 110,5 x 114,3 mm
  • Displacement: 8,8 L
  • Cooling System: Coolant
  • Lube Oil Specifications: API ≥SM, SAE 5W30
  • Compression Ratio: 10,1:1
  • Fuel Consumption ESP: 33,14 Nm3/h
  • Fuel Consumption 100% PRP: 30,13 Nm3/h
  • Total oil capacity including tubes, filters 7,6 L
  • Governor Type Electrical
  • Air Filter Type Dry
  • Natural Gas engine
  • 4-stroke cycle
  • Water-cooled
  • 12V electrical system
  • Dry air filter
  • Radiator with pusher fan
  • HTW sender
  • LOP sender
  • Electronic governor
  • Hot parts protection
  • Moving parts protection
  • Self-excited and self-regulated
  • 4 poles
  • AVR governor
  • IP23 protection
  • H class insulation
  • Single drive-shaft
  • Flexible disc coupling
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • 4-pole thermal magnetic circuit breaker
  • Battery Switch
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • Steel chassis
  • Oil sump extraction kit
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Steel industrial silencer -15db(A) attenuation
  • Steel residential silencer -35db(A) attenuation. (opcional)
  • Manual shut-off valve
  • Gas filter
  • Double solenoid valve
  • Primary pressure regulator
  • Secondary pressure regulator (Zero pressure regulator)
  • Low pressure switch
  • Inlet pressure manometer
  • Outlet pressure manometer
  • Special Start/Stop sequence
  • High pressure regulator (opcional)
  • High pressure switch (opcional)
  • Generator
  • Poles: 4
  • Connection type (standard): Star-series
  • Mounting type: S-3 11"1/2
  • Insulation: H class
  • Enclosure (according IEC-34-5): IP23
  • Exciter system: Self-excited, brushless
  • Voltage regulator: A.V.R. (Electronic)
  • Bracket type: Single bearing
  • Coupling system: Flexible disc
  • Coating type: Standard (Vacuum impregnation)
  • - Electrical system.
  • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
  • Battery Switch
  • 4-pole thermal magnetic circuit breaker
  • Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
  • Battery charger (standard on gensets with automatic control panels)
  • Heating resistor (standard on sets with automatic control panels)
  • Battery charger alternator with ground connection
  • Starter battery/ies installed (cables and bracket included)
  • Ground connection electrical installation with connection ready for ground spike (not supplied)
  • - Open set version.
  • Steel chassis
  • Oil sump extraction kit
  • Emergency stop button
  • Anti-vibration shock absorbers
  • Steel industrial silencer -15db(A) attenuation
  • Steel residential silencer -35db(A) attenuation. Optional
  • - Gas ramp.
  • Manual shut-off valve
  • Gas filter
  • Double solenoid valve
  • Primary pressure regulator
  • Secondary pressure regulator (Zero pressure regulator)
  • Low pressure switch
  • Inlet pressure manometer
  • Outlet pressure manometer
  • Special Start/Stop sequence
  • High pressure regulator Optional
  • High pressure switch Optional
  • - EXHAUST SYSTEM.
  • Maximum exhaust temperature: 705 ºC
  • Exhaust Gas Flow: 18,76 m3/min
  • Maximum allowed back pressure: 10,2 kPa
  • - NECESSARY AMOUNT OF AIR.
  • Intake air flow: 348,6 m3/h
  • Alternator fan air flow: 0,514 m3/s
  • - STARTING SYSTEM.
  • Starting power: 1,7 kW
  • Starting power: 2,31 CV
  • Recommended battery: 115 Ah
  • Auxiliary Voltage: 12 Vdc
  • - FUEL SYSTEM
  • Fuel Oil Specifications: Natural Gas
  • - Dimensions.
  • Length: 2.900 mm
  • Height: 1.500 mm
  • Width: 900 mm
  • Maximum shipping volume: 3,91 m3
  • Weight with liquids in radiator and sump: 1.180 kg

Power


kVA

95
 
106
Prime power  (95 - 574)
Stand by  (106 - 675)

kW

76
 
85
Prime power  (76 - 459)
Stand by  (85 - 540)
 

dimensions


 
dimensions
Long (A)
290
Width (B)
90
High (C)
150
 

Weight


 
Weight
Weight with liquid in radiator and carter

1.180
 

Fuel capacity